Zoom In
Zoom Out
Enlarge
*Product images are for illustrative purposes only and may differ from the actual product.
25kV - EPR Insulation, MV-105-133% Insulation Level
EPR Insulation - PVC Jacket
MV-105 - 25kV at 133% Insulation
Shielded - Single Conductor
Construction |
Category Conductor Description |
Annealed bare copper
Compact, Class B stranding
|
Extruded Strand Shield |
Extruded thermoset semi-conducting stress control layer over conductor
|
Category Insulation Description |
Ethylene Propylene Rubber (EPR), colored to contrast with the black conducting shield layers
|
Extruded Insulation Shield |
Thermoset semi-conducting polymeric layer free stripping from insulation
|
Metallic Shield |
5 mil annealed copper tape with an overlap of 25%
|
Category Jacket Description |
Low friction, lead-free, flame-retardant, moisture, and sunlight resistant Polyvinyl Chloride (PVC)
|
-
Suitable for use in wet and dry locations when installed in accordance with NEC
-
For aerial, direct burial, conduit, open tray, and underground duct installations
-
For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4(A)(5)
-
National Electric Code (NEC)
-
UL 1072
-
UL listed as Type MV-105 for use in accordance with NEC
-
UL 1685
-
IEEE 1202
-
OSHA Acceptable
Part Number Table
Part # |
Gauge |
Stranding |
Insulation Thickness |
Jacket Thickness |
Nominal OD over Insulation |
Outside Diameter Inches |
Material Weight (Lbs./M') |
MVE41/001 |
1/0 |
19 |
0.345 |
0.08 |
1.08 |
1.31 |
1086.4 |
MVE42/001 |
2/0 |
19 |
0.345 |
0.08 |
1.12 |
1.41 |
1304 |
MVE43/001 |
3/0 |
19 |
0.345 |
0.08 |
1.17 |
1.46 |
1461 |
MVE44/001 |
4/0 |
19 |
0.345 |
0.08 |
1.22 |
1.45 |
1531.3 |
MVE425001 |
250 |
37 |
0.345 |
0.08 |
1.28 |
1.57 |
1826 |
MVE435001 |
350 |
37 |
0.345 |
0.08 |
1.37 |
1.67 |
2235 |
MVE450001 |
500 |
37 |
0.345 |
0.11 |
1.5 |
1.85 |
2934 |
MVE475001 |
750 |
61 |
0.345 |
0.11 |
1.68 |
2.06 |
3962 |
MVE4100001 |
1000 |
61 |
0.345 |
0.11 |
1.84 |
2.22 |
4917 |
Note: The data shown is approximate and subject to standard industry and manufacturer tolerances