ALUSE Aluminum, XLPE Insulated 600V90°C Dry, Wet, Direct Burial

Choose Favorites List
Zoom In Zoom Out Enlarge

*Product images are for illustrative purposes only and may differ from the actual product.

    ALUSE Aluminum, XLPE Insulated 600V90°C Dry, Wet, Direct Burial

    Construction
    Category Conductor Description Compact stranded AA-8000 series aluminum alloy per ASTM B801 or ASTM B836 and ASTM B800
    Category Insulation Description Black, thermoset cross-linked polyethylene (XLPE) meeting the requirements of RHH/RHW-2/USE-2 per UL 44 and UL 854

    Questions & Answers

    Ask a Question

    Part Number Table

    Part # Gauge Insulation Thickness Outside Diameter Inches
    ALUSE-2-6 6 60 0.29
    ALUSE-2-4 4 60 0.34
    ALUSE-2-2 2 60 0.39
    ALUSE-2-1 1 80 0.46
    ALUSE-2-1/0 1/0 80 0.5
    ALUSE-2-2/0 2/0 80 0.54
    ALUSE-2-3/0 3/0 80 0.59
    ALUSE-2-4/0 4/0 80 0.64
    ALUSE-2-250 250 95 0.71
    ALUSE-2-350 350 95 0.81
    ALUSE-2-500 500 95 0.93
    ALUSE-2-600 600 110 1.04
    ALUSE-2-750 750 110 1.13